Mitsubishi

VRV

  • Connect TB3 indoor cabling to terminal block TB5 A&B. Must be connected to the indoor loop of the units its being interlocked with
  • Address as per schematic or last indoor unit +1

Standalone

  • Interlocking with Mr Slim, use interface plug (taped to top of unit). Connect plug to indoor PCB and connect to TM2 1&2 on HRV unit. Settings and interlocking accessable though Mr Slim wall controller under losnay
  • PAC88 connected directing to TM2 1&2
  • Dry contact conected to TM2 1&3

Manual Speed Control

  • PAC88 connected to CN16
    • Brown to Red = High
    • Brown to Orange = Low
    • Brown to Green = Bypass

Run Relay

  • TM4 9&10 Dry Relay contact

Dip Switch Settings

SW2-5 = SA Fan Low Speed (on for low)

SW2-6 = EA Fan Low Speed (on for low)