Mitsubishi
VRV
- Connect TB3 indoor cabling to terminal block TB5 A&B. Must be connected to the indoor loop of the units its being interlocked with
- Address as per schematic or last indoor unit +1
Standalone
- Interlocking with Mr Slim, use interface plug (taped to top of unit). Connect plug to indoor PCB and connect to TM2 1&2 on HRV unit. Settings and interlocking accessable though Mr Slim wall controller under losnay
- PAC88 connected directing to TM2 1&2
- Dry contact conected to TM2 1&3
Manual Speed Control
- PAC88 connected to CN16
- Brown to Red = High
- Brown to Orange = Low
- Brown to Green = Bypass
Run Relay
- TM4 9&10 Dry Relay contact
Dip Switch Settings
SW2-5 = SA Fan Low Speed (on for low)
SW2-6 = EA Fan Low Speed (on for low)