Test Mode
- Hold BS2 for 5 Sec, T01 will flash up
To Reset VRV Systems
1- Turn off indoors via switchboard
2- Turn off outdoor via isolator
3- push and hold BS3, while holding BS3 turn outdoor isolator ON and hold BS3 for 30 seconds.
4- Release BS3 and turn on indoor unit circuit
5- Wait for 3 0’s on outdoor unit (BS1,BS2,BS3) to stop flashing and turn solid. This can take a while.
6- Once all 0s are solid hold BS2 for 5 seconds to initiate test mode.
To Check How Many Indoor the Outdoor Can See
- Press BS1 putton once (100)
- Press BS2 10 times (110)
- Press BS3 once
The number shown is the number of units registering