Wiring
T10 loops to switch/relay and back to T13
T10 can loop to Relays 2 & 3 for 24v Neon if needed with T11 as 24v Neutral
Loop T11 & 12
Loop T10 to T16 for safety interlock
T2 & T3 for 0-10v speed input
T4 is +10v for 0-10v Speed Pot
Commissioning
1. Setup Assistant
2. Commissioning Drive
9905 Motor Nom Voltage = 415v
9906 Motor Nom Current = FLA of Motor
9907 Motor Nom Frequency = 50Hz
9908 Motor Nom Speed = RPM of Motor
9909 Motor Nom Power = kW of Motor
9902 Applic Macro = HVAC Defult
Do You Want To Use Auto/Off/Man Switch = No
Do You Want To Continue with Reference Setup = Continue
Reference Setup = Yes
2007 Min Freq =20Hz
2008 Max Freq = 50Hz
Do You Want To Continue with Start/Stop Setup = Skip
Do You Want To Conitune with Protection Setup = Yes
2003 Max Current = FLA of Motor
Do You Want to Continue with Const Speed Setup = Skip
Do You Want to Continue with PID Setup = Skip
Do You Want To Continue with Low Noise Setup = Skip
Do You Want to Continue with Panel Display Setup = Skip
Do You Want To Continue with Timed FUNCS Setup = Skip
Do You Want To Continue with Relay & Analogue Output Setup = No
Do You Want To Upload to Panel = Yes
Drive is now ready to use
Notes: Every-time Application Macro is changed or OK is pressed all settings will reset to default